DC Coupling Reactors
Coupling (equalizing) reactors type ED2I are used in systems in which rectifiers operate in parallel within multiphase systems. Their main task is to equalize currents flowing between parallel rectifier bridges, which is particularly important in situations where asymmetry of output voltages of individual rectifiers occurs.
- Reduction of current ripple in the DC circuit
- Equalization of currents between parallel rectifier bridges
- Protection of semiconductor components against excessive load
- More stable operation of the rectifier system
- Increased durability and reliability of the entire DC system
- Railway industry, including traction systems and substation rectifiers
- Heavy industry
- Power electronics and drive systems
- High-power DC power supply systems
- Parallel rectifier systems used in power engineering and automation
Product for:
Details:
| Design | Chokes are produced in accordance with standard: EN/IEC 60076-6 |
|---|---|
| Insulation class |
F(155oC) - standard |
| Climativ class / Environmental class |
C1/E0 - land design; C2/E1 - maritime design |
| Ambient temperature | 40oC |
| Protection degree | IP 00 |
| Pulsation content | <= 10% - standard |
| Pulsation frequency | 300 Hz |
| Rated voltage | up to 750 V (230 V standard) |
| Overload | 110% In |
| Terminals | screw terminal blocks or cable lugs or copper bus bars |
| Fastening | by means of angles |
Technical sketch
![]() |
| Exemplary design |
Dimension table
Technical data of sample DC interface chokes ED2I
| Type of choke | Inductance [mH] |
Current [A] |
L [mm] |
B [mm] |
H [mm] |
d [mm] |
e [mm] |
f [mm] |
Weight [kg] |
|---|---|---|---|---|---|---|---|---|---|
| ED2I | 2 x 0,024 | 2 x 135 | 120 | 131 | 159 | 110 | 57 | 8 x 12 | 5,1 |
| ED2I | 2 x 0,13 | 2 x 130 | 160 | 185 | 208 | 110 | 122 | 8 x 12 | 16 |
| ED2I | 2 x 0,049 | 2 x 250 | 200 | 225 | 270 | 140 | 145 | 11 x 15 | 29 |
| ED2I | 2 x 0,016 | 2 x 518 | 280 | 266 | 425 | 240 | 181 | 11 x 15 | 69 |
| ED2I | 2 x 0,9 | 2 x 700 | 500 | 505 | 717 | 400 | 300 | 13 x 18 | 360 |