Medical transformers
ET3MED transformers are specifically designed to supply medical equipment in hospital group 2 rooms, where even minimal current flowing through a patient’s body may pose a serious risk to life or health. The transformer design complies with PN/EN 61558-2-15:2011, ensuring the highest level of electrical safety.
- Maximum safety for patients and medical staff
- Enhanced power supply reliability in critical applications
- Protection of sensitive medical equipment against disturbances and overvoltages
- Full compliance with applicable standards and industry regulations
- Medical sector – in particular group 2 medical locations
Custom Design
Manufacturing a transformer with parameters other than those specified in the catalogue is possible upon prior consultation.
Download datasheets
Product code

Details:
| Design | Three-phase isolating transformers ET3MED are produced in accordance with requirements of PN/EN 61558-2-15:2011 |
|---|---|
| Insulation class |
T 40E |
| Protection degree | IP 00 |
| Protection class | I |
| Frequency | 50 Hz |
| Primary voltage | 3 x 400 V |
| Secondary voltage | 3 x 230 V |
| Short-circuit voltage | <3%Un |
| No-load current | <3%In |
| Leakage current | max. 0,2 mA |
| Inrush current | 12 x In max |
| Vector group | YNyn0 |
| Fastening | by means of angles |
Technical sketch
![]() |
![]() |
![]() |
| Standard design | Connection_diagram | |
Dimension table
Technical data of three-phase isolation transformers ET3MED
| Type | Power [kVA] |
In [A] |
DELTA °Pfe [W] |
DELTA °Pcu [W] |
uz |
io |
Ibezp [A] gG |
L [mm] |
Bmax [mm] |
H [mm] |
d [mm] |
e [mm] |
k [mm] |
w [mm] |
f [mm] |
Weight [kg] |
Design |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| ET3MED - 2,5 | 2,5 | 3,7 | 28 | 60 | 2,8 | 1,9 | 6 | 300 | 180 | 320 | 240 | 145 | 177 | 258 | 11 x 15 | 42 | A |
| ET3MED - 3,15 | 3,15 | 4,7 | 32 | 80 | 2,9 | 1,8 | 10 | 300 | 200 | 320 | 240 | 160 | 192 | 258 | 11 x 15 | 49 | A |
| ET3MED - 4,0 | 4,0 | 6,0 | 38 | 100 | 2,6 | 1,7 | 10 | 300 | 210 | 320 | 240 | 171 | 203 | 258 | 11 x 15 | 53 | A |
| ET3MED - 5,0 | 5,0 | 7,5 | 39 | 125 | 2,9 | 1,7 | 16 | 360 | 190 | 365 | 300 | 146 | 178 | 305 | 11 x 21 | 63 | B |
| ET3MED - 6,3 | 6,3 | 9,4 | 40 | 160 | 2,8 | 1,7 | 16 | 360 | 200 | 365 | 300 | 161 | 178 | 305 | 11 x 21 | 70 | B |
| ET3MED - 8,0 | 8,0 | 12,0 | 51 | 210 | 2,9 | 1,6 | 20 | 420 | 220 | 415 | 370 | 166 | 208 | 356 | 11 x 21 | 89 | B |
| ET3MED - 10,0 | 10,0 | 14,9 | 60 | 220 | 2,6 | 1,6 | 25 | 420 | 230 | 420 | 370 | 181 | 223 | 356 | 11 x 21 | 106 | B |
Note:
Manufacturer reserves the right to make changes resulting from the continuous development of products offered.
If requested in advance, it is possible to manufacture transformer in other version.