Power transformers
Low-voltage power transformers are designed for reliable power supply of electrical equipment operating across various industrial sectors. As standard, they are adapted for mounting using fixing brackets, enabling easy integration with the installation. The number of taps on the primary and secondary sides is selected individually according to customer requirements, allowing precise adjustment of transformer parameters to operating conditions.
- Enhanced energy security through stable operation and effective insulation
- Protection of equipment against overvoltages, disturbances and failures
- Optimization of energy costs through high efficiency and reliability
- Flexible configuration – selectable taps, terminal arrangement and enclosure variant
- Easy installation and integration with existing systems
- Robust design ensuring long service life in demanding applications
- Railway industry
- Oil & gas industry
- Heavy industry
- Renewable energy sources
- Mining industry
- Power electronics and drive systems
Custom Design
Manufacturing a transformer with parameters other than those specified in the catalogue is possible upon prior consultation.
Download datasheets
Product code
Details:
| Design | Power transformers are produced in accordance with requirements of: EN/IEC 60726; EN/IEC 60076 |
|---|---|
| Insulation class | H(180°C) |
| Climatic class /environmental class |
C1/E0 - land design; C2/E1 - maritime design |
| Ambient temperature | 40oC |
| Protection degree | IP 00 |
| Protection class | I |
| Frequency | 50/60 Hz |
| Vector group | Dyn5 - standardowo |
| Primary voltage | up to 1000 V |
| Secondary voltage | up to 1000 V |
| Terminals | screw terminal blocks or cable lugs or copper bus bars |
Technical sketch
![]() |
![]() |
| Design for the power up to 160kVA | |
![]() |
![]() |
| Design for the power above 160kVA | |
Dimension table
Technical data of power transformers typ ET3S, insulation class H, voltage ratio 400V//400V**
| Type | Power [kVA] |
L [mm] |
B [mm] |
H [mm] |
d [mm] |
e [mm] |
f [mm] |
Weight [kg] |
|---|---|---|---|---|---|---|---|---|
| ET3S_* - 40 | 40 | 540 | 320 | 545 | 490 | 220 | 13 x 18 | 171 |
| ET3S_* - 50 | 50 | 540 | 350 | 545 | 490 | 240 | 13 x 18 | 202 |
| ET3S_* - 63 | 63 | 540 | 370 | 545 | 490 | 260 | 13 x 18 | 235 |
| ET3S_* - 75 | 75 | 690 | 390 | 615 | 590 | 210 | 13 x 18 | 271 |
| ET3S_* - 80 | 80 | 690 | 400 | 615 | 590 | 220 | 13 x 18 | 288 |
| ET3S_* - 100 | 100 | 690 | 380 | 615 | 590 | 230 | 13 x 18 | 330 |
| ET3S_* - 115 | 115 | 690 | 410 | 615 | 590 | 260 | 13 x 18 | 380 |
| ET3S_* - 120 | 120 | 720 | 400 | 715 | 620 | 250 | 17 x 25 | 390 |
| ET3S_* - 125 | 125 | 720 | 410 | 715 | 620 | 250 | 17 x 25 | 400 |
| ET3S_* - 160 | 160 | 720 | 440 | 715 | 620 | 290 | 17 x 25 | 495 |
| ET3S_* - 200 | 200 | 980 | 460 | 860 | 700 | 375 | 4xfi17 | 660 |
| ET3S_* - 225 | 225 | 980 | 460 | 860 | 700 | 375 | 4xfi17 | 690 |
| ET3S_* - 250 | 250 | 1035 | 470 | 910 | 760 | 375 | 4xfi17 | 790 |
| ET3S_* - 315 | 315 | 1080 | 480 | 980 | 760 | 375 | 4xfi17 | 915 |
| ET3S_* - 400 | 400 | 1140 | 505 | 1010 | 760 | 394 | 4xfi17 | 1105 |
| ET3S_* - 500 | 500 | 1245 | 545 | 1100 | 760 | 416 | 4xfi17 | 1350 |
| ET3S_* - 630 | 630 | 1290 | 555 | 1210 | 760 | 416 | 4xfi17 | 1685 |
| ET3S_* - 800 | 800 | 1410 | 600 | 1220 | 760 | 433 | 4xfi17 | 1980 |
| ET3S_* - 1000 | 1000 | 1455 | 610 | 1420 | 760 | 433 | 4xfi17 | 2440 |
| ET3S_* - 1250 | 1250 | 1620 | 650 | 1390 | 760 | 473 | 4xfi17 | 3080 |
| ET3S_* - 1600 | 1600 | 1670 | 700 | 1500 | 760 | 473 | 4xfi17 | 3580 |
*) - for transformer design with climatic/environmental class C2/E1 (maritime design W/3 or tropical design T/3) the letter "M" or "G" ought to be added depending on final application
**) - this table was prepared basing on the technical specification for transformer with voltage ratio 400//400 at 50 Hz and operating under normal conditions. For other conditions and data the values may change
Note:
Manufacturer reserves the right to make changes resulting from the continuous development of products offered.
If requested in advance, it is possible to manufacture transformer in other version.
Andrzej Pietkiewicz