Three-phase line reactors ED3N
Function
The line reactor increases the impedance at the connection point of the frequency converter. As a result, the current consumed by the converter has a lower value of the THDi distortion coefficient, which reduces its effective value. ED3N reactor helps to eliminate negative effects of transients, limiting steepness and peak value of current pulses. 4% reactors are mainly used in drives without a built-in DC-link choke.
The line reactor increases the impedance at the connection point of the frequency converter. As a result, the current consumed by the converter has a lower value of the THDi distortion coefficient, which reduces its effective value. ED3N reactor helps to eliminate negative effects of transients, limiting steepness and peak value of current pulses. 4% reactors are mainly used in drives without a built-in DC-link choke.
Benefits | Application |
---|---|
|
|
Schemat typowej aplikacji
Special execution
Products with parameters exceeding the catalogue card can be made upon prior contact
Product for:
Details:
Rated current | 3-1250 A |
---|---|
Rated voltage |
400 V |
Rated frequency | 50 Hz |
Overloadability | 110% In (continuous) 160% In (momentary) |
Cooling | AN - air natural |
Ambient temperature | 40°C – standard design 45°C – maritime design ≥50°C – special design |
Insulation class | F (155°C) |
Winding material | Copper |
Standard equipment | NC temperature switch from 700 A (355 kW) - 2% reactors from 500 A (250 kW) - 4% reactors |
Mounting | Standing, vertical |
Degree of protection | IP00 |
Applied standards | PN-EN 61558-20, PN-EN 60076-6 |
*- UL approved insulation system