Single-phase power transformers ET1S ** with the power between 2,0 and 100 kVA

Power transformers are assigned for supplying electric devices, and for application in various industrial branches. In standard design, the transformers are adjusted to fastening by means of a base welded into core or screwed angles. If agreed, the transformers may have more tappings. The windings terminals may be placed on one side only, or on both sides of a transformer.
Upon request, the transformers may be assembled in enclosures with the protection degree of IP 23, IP 44 and IP 54 with the possibility to insert supply cables through glands.

Download catalog card in PDF

Product for:

Details:

Design Power transformers are produced in accordance with requirements of:
EN/IEC 60076
Insulation class

B(130oC) - standard up to 5 kVA; F(155oC) - standard above 5 kVA

Climatic class
/environmental class

C1/E0 - land design; C2/E1 - maritime design

Ambient temperature 40oC
Protection degree IP 00
Protection class I
Frequency 50/60 Hz
Primary voltage up to 1000 V
Secondary voltage up to 1000 V
Terminals screw terminal blocks or cable lugs or copper bus bars
Fastening by means of angles

 

Technical sketch


Wykonanie A dla mocy do 6,3 kVA
Design A
Wykonanie B dla mocy powyżej 6,3 kVA
Design B

Dimension table


Technical data of single-phase power transformers ET1S **

Type Power
[kVA]
L
[mm]
B
[mm]
H
[mm]
d
[mm]
e
[mm]
f
[mm]
Weight
[kg]
Design
ET1S_* - 2,0 2,0  174  140  240  116 114 11 x 15  17 A
ET1S_* - 2,5  2,5  174  152  240  116  126  11 x 15  21 A
ET1S_* - 3,0  3,0  200  165  280  140  133  11 x 15  23 A
ET1S_* - 3,5  3,5  200  177  280  140  145  11 x 15  27 A
ET1S_* - 4,0  4,0  200  192  280  140  160  11 x 15  30 A
ET1S_* - 5,0  5,0  240  165  333  200  127  11 x 15  35 A
ET1S_* - 6,3  6,3  240  180  333  200  142  11 x 15  40 A
ET1S_* - 7,5  7,5  280  200  475  240  151  11 x 15  46 A
ET1S_* - 8,0  8,0 280  200  475  240  151  11 x 15  48 A
ET1S_* - 10,0  10,0  280  210  480  240  168  11 x 15  56 A
ET1S_* - 12,0  12,0  280  220  480  240  178  11 x 15  63 A
ET1S_* - 15,0  15,0  320  300  425  270  190  13 x 18  74 B
ET1S_* - 16,0  16,0  320  300  425  270  190  13 x 18  76 B
ET1S_* - 20,0  20,0  360  330  480  310  220  13 x 18  98 B
ET1S_* - 25,0  25,0  360  340  480  310  240  13 x 18  120 B
ET1S_* - 30,0  30,0  360  350  480  310  240  13 x 18  130 B
ET1S_* - 40,0  40,0  360  400  480  310  270  13 x 18  160 B
ET1S_* - 50,0  50,0  460  420  550  360  220  13 x 18  190 B
ET1S_* - 63,0  63,0  460  450  550  360  240  13 x 18  218 B
ET1S_* - 75,0  75,0  460  480  550  360  270  13 x 18  254 B
ET1S_* - 80,0  80,0 480  430  640  380  260  17 x 25  268 B
ET1S_* - 100,0  100,0  480  460  640  380  290  17 x 25  334 B

*) - for transformer design with climatic/environmental class C2/E2 (maritime design W/3 or tropical design T/3) the letter "M" or "G" ought to be added depending on final application
**) - this table was prepared basing on the technical specification for transformer with voltage ratio 400//400 operating under normal conditions. For other conditions and data the values may change

Note:

Manufacturer reserves the right to make changes resulting from the continuous development of products offered.

If requested in advance, it is possible to manufacture transformer in other version.

Obudowa leżąca IP 23 dla urządzeń jednofazowych

for horizontal mounting IP23

Obudowa stojąca IP 23 dla urządzeń jednofazowych

for vertical mounting IP23

Obudowa naścienna IP 23 dla urządzeń jednofazowych

wall mounted IP23

Obudowa stojąca IP 44 dla urządzeń jednofazowych

vertical design IP44

Obudowa stojąca IP 54 dla urządzeń jednofazowych

vertical design IP54

Kurt Schenk,
Andrzej Pietkiewicz
2020
Case Study
January 2022
Case Study Praxis
635.37 kB PDF
Case Study
May 2022
ask about this product

Quality supported by certificates

ELHAND PQ – Elhand Power Quality Harmonic Simulation Software

ELHAND PQ is charge-free software that allows to find the optimum solution for different configurations and parameters of your circuit without the need for costly measurements, tests and analyses. More >>

Important: The website uses cookies.

We use information saved using cookies and similar technologies, including for advertising purposes and statistical and to adapt the website to the individual needs of users. the use of website without changing the cookie settings means that they will be stored on your device final. You can change your cookie settings at any time. More information can be found in our "Cookies Policy".