Single-phase safety isolating transformers ET1o ** with the power between 2,0 and 10 kVA
Safety isolating transformers are assigned for supplying electric devices with safe voltage. In standard design, the transformers are adjusted to fastening by means of screwed angles.
If agreed, the transformers may have more tappings. The windings terminals may be placed on one side only, or on both sides of a transformer.
Upon request, the transformers may be assembled in enclosures with the protection degree of IP 23, IP 44 and IP 54 with the possibility to insert supply cables through glands. Standard enclosures have powder coating - colour RAL 7032.
Product for:
- Railway Industry
- Oil & Gas Industry
- Mining Industry
- Maritime Industry
- Heavy Industry
- Power Electronics and Drive Systems
- Power Quality
- Renewable Energy Sources
Details:
Design | Safety isolating transformers produced in accordance with requirements of EN/IEC 61558-2-6 |
Insulation class |
B(130ºC) - standard up to 5 kVA, F(155ºC) - standard above 5 kVA |
Climatic class / environmental class |
C1/E0 - land design; C2/E1 - maritime design |
Ambient temperature | 40oC |
Protection degree | IP 00 |
Protection class | I |
Frequency | 50/60 Hz |
Primary voltage | up to1000 V |
Secondary voltage | up to 50 V |
Terminals | screw terminal blocks with the cross section from 1,5 mm2 up to 150 mm2 or copper bus bars |
Fastening | by means of angles |
Technical sketch
Design A for the power up to 6,3 kVA |
Design B for the power more than 6,3 kVA |
Design B for secondary current above 300 A |
Dimension table
Technical data of single-phase safety isolating transformers ET1o **
Type | Power [kVA] |
L [mm] |
B [mm] |
H [mm] |
d [mm] |
e [mm] |
f [mm] |
Weight [kg] |
Design |
---|---|---|---|---|---|---|---|---|---|
ET1o_* - 2,0 | 2,0 | 178 | 140 | 240 | 128 | 114 | 11 x 15 | 18 | A |
ET1o_* - 2,5 | 2,5 | 178 | 152 | 240 | 128 | 126 | 11 x 15 | 21 | A |
ET1o_* - 3,0 | 3,0 | 200 | 165 | 271 | 140 | 133 | 11 x 15 | 24 | A |
ET1o_* - 3,5 | 3,5 | 200 | 177 | 271 | 140 | 145 | 11 x 15 | 27 | A |
ET1o_* - 4,0 | 4,0 | 200 | 192 | 271 | 140 | 160 | 11 x 15 | 30 | A |
ET1o_* - 5,0 | 5,0 | 240 | 165 | 323 | 200 | 127 | 11 x 15 | 36 | A |
ET1o_* - 6,3 | 6,3 | 240 | 180 | 323 | 200 | 142 | 11 x 15 | 41 | A |
ET1o_* - 7,5 | 7,5 | 280 | 260 | 425 | 240 | 151 | 11 x 15 | 46 | B |
ET1o_* - 8,0 | 8,0 | 280 | 260 | 425 | 240 | 151 | 11 x 15 | 57 | B |
ET1o_* - 10 | 10,0 | 280 | 275 | 425 | 240 | 168 | 11 x 15 | 64 | B |
*) - for transformer design with climatic/environmental class C2/E1 (maritime design W/3 or tropical design T/3) the letter "M" or "G" ought to be added depending on final application
**) - this table was prepared basing on the technical specification for transformer with voltage ratio 230//24 operating under normal conditions. For other conditions and data the values may change
Note:
Manufacturer reserves the right to make changes resulting from the continuous development of products offered.
If requested in advance, it is possible to manufacture transformer in other version.